Mounting Positions WTT Series heat exchangers should be mounted in such a way that there is sufficient room around the heat exchanger to perform maintenance work. It is recommended that WTT heat exchangers be mounted in the vertical position (fig. 1). Vertical mounting position - recommended Optional positions for single phase only For all two-phase applications, the heat exchanger should always be mounted vertically. If this is not possible, contact the factory for recommendations on mounting. A red color label indicates the primary side for liquid-to-liquid applications. A blue color label indicates the refrigerant side for refrigerant applications (fig. 1). Preferably, the heat exchanger should be supported by a bracket or support. The unit should not be supported solely by the piping. Insure that severe vibrations or pulsation cannot be transmitted to the heat exchanger by installing vibration absorbers in the piping and using vibration absorbing material between the heat exchanger and the equipment. |